SPECIALTY GAS MANIFOLDS - CS3000
specs CS3000 Technical Data Sheet  CS3000 Installation & Operation Manual

CS3000 Series Manifolds:



The CS3000 Series Automatic Changeover Stations are designed to provide a continuous supply of high purity gases. The system automatically changes from a depleted bank of cylingers in service to the full reserve bank without an interrruption of gas supply. A simple rotation of the primary bank knob resets the unit once the depleted bank of cylinders has been replaced. The standard outlet regulator maintains a constant line pressure, even during the changeover process. The optional remote alarm box indicates when the pressure of each bank is either normal or low.

Features:

  • Automatic changeover for a continuous supply.
  • In-board line regulator for stable delivery pressure.
  • Brass or stainless steel construction.
  • For inert, toxic, oxidant or corrosive gases.

 

CS3000 specialty manifold diagram

MODEL CS3000 Series
Brass Construction
CS3000 Series
Stainless Steel Construction
Maximum Inlet pressure 3000 PSIG 3000 PSIG
Outlet Pressure Range See part # matrix See Part # matrix
Inlet Connection Fitting Gas related brass CGA nut & nipple Gas related Type 316 stainless steel CGA nut & nipple
Gas Service Outlet Connection 1/4" compression S/S 1/4" compression S/S
Vent Valve Outlet Connection 1/4" Male NPT 1/4" Male NPT
Operating Temperature -40°F to -140°F -40°F to -140°F
Pressure Gauge Dial & Material 2"-dial.brass 2"-dial. type 316 stainless steel
Fitting Size & Material 1/4" NPS, brass 1/4" NPS, Type 316 Stainless Steel
Pressure
Body
Diaphragm
Filter


Seats
Seals


Brass Bar Stock
Type 316L Stainless Steel
10-micron
Nickel-plated sintered bronze
PCTFE
Teflon

Type 316L Stainless Steel Bar Stock
Type 316L Stainless Steel
40-micron
Type 316L Stainless Steel

PCTFE
Teflon
Vent Valves
Body
Seats

Seals


Forged brass UNS 37700
Nylon, Zytel 101 or Celanese 1000-1
Virgin Teflon

Type 316 Stainless Steel
PFA

PFA
HOW TO ORDER
Box_1   Box_2   Box_3   Box_4   Box_5   Box_6   Box_7   Box_8
CS3000
-
 
-
 
-
 
-
 
-
 
-
 
-
 
How to Fill Out the Boxes
Box 1
Box 2
Box 3
Box 4
Series
(inlet pressure)


Standard Series
CS3000 = 3000 psi

Optional Series
CS375 = 375 psi
(combustible gases)
CS5000 = 5000 psi
CS6000 = 6000 psi
Typical Fluid

2 = Air
5 = Helium
6 = Hydrogen
7 = Nitrogen

Most specialty gases
can be specified
including acetylene
and other LPG.
Outlet Pressure

15 = 1-15 PSIG
25 = 2-25 PSIG
50 = 2-50 PSIG
100 = 5-100 PSIG
150 = 5-150 PSIG
250 = 10-250 PSIG
500 = 30-500 PSIG

Other: Please Specify
Regulator

B1 = Brass Regulators

S1 = Stainless Steel Regulators
Box 5
Box 6
Box 7
Box 8
Left Bank
# of cylinders (maximum 6)
Right Bank
# of cylinders (maximum 6)
Flexible Hoses

NH = Thermoplastic (Nylon) steel fittings

TH = Teflon core, brass fittings, S/Steel braid

SH = All Stainless Steel
Options

RA2 = Standard Alarm
RF2 = Wireless Alarm
V V = Vent Valve
AG = Hose Armor
QC = Zipnut Q/C
HT = Hand Tight Nut

For more information, call Western Customer Service
at 1-800-783-7890 for technical data sheets

 

 


 

home | about us | distributor info | wholesalers | service providers
industrial manifolds | med manifolds | spec manifolds | manifold accessories
news | faqs | references


 
 
powered by Vertical Lift Web Designs